Page MenuHomePhabricator

check mw1203 power supply redundancy
Closed, ResolvedPublic

Description

mw1203 has an open power supply alert in icinga. The most recent related ipmi sel events are:

31  | Jan-05-2015 | 17:06:12 | Status           | Power Supply             | Power Supply Failure detected ; OEM Event Data2 code = 07h
32  | Jan-05-2015 | 17:06:14 | Status           | Power Supply             | Presence detected
33  | Jan-05-2015 | 17:06:14 | Status           | Power Supply             | Configuration error
34  | Jan-05-2015 | 17:06:36 | Status           | Power Supply             | Power Supply Failure detected ; OEM Event Data2 code = 07h
35  | Jan-05-2015 | 17:06:39 | Status           | Power Supply             | Presence detected
36  | Jan-05-2015 | 17:06:39 | Status           | Power Supply             | Power Supply input lost (AC/DC)
37  | Jan-05-2015 | 17:06:44 | Status           | Power Supply             | Power Supply input lost (AC/DC)

Event Timeline

Cmjohnson claimed this task.
Cmjohnson subscribed.

This PSU on the surface appears to be fine, no LED's and racadm showed it normal. The mgmt U?I showed PS1 failed. Replaced from a recent decom. (out of warranty)