Check cp4026 power supply redundancy
Closed, ResolvedPublic

Description

cp4026 has an open power supply alert in icinga. The most recent related ipmi events are:

9   | Oct-12-2017 | 00:03:42 | Status           | Power Supply             | Power Supply input lost (AC/DC)
10  | Oct-12-2017 | 00:03:42 | PS Redundancy    | Power Supply             | Redundancy Lost
11  | Oct-12-2017 | 00:05:07 | Status           | Power Supply             | Power Supply input lost (AC/DC)
12  | Oct-12-2017 | 00:05:17 | Status           | Power Supply             | Power Supply input lost (AC/DC)

Event Timeline

RobH claimed this task.
RobH triaged this task as Medium priority.
RobH added a subscriber: RobH.

The power plug on the PDU tower side was slightly unseated. The pdu towers provided by unitedlayer lack any kind of anchoring clip to hold the cables in place, so my replacing other servers in the same rack last week resulted in my bumping the cables and this happening.

Fixed!