Page MenuHomePhabricator

eqiad - eqord Telia link down - IC-314533
Closed, ResolvedPublic

Description

The eqiad - eqord Telia link went down and it did not look planned. There was no mail from Telia regarding IC-314533 since Jan 9.


https://icinga.wikimedia.org/cgi-bin/icinga/extinfo.cgi?type=2&host=cr2-eqiad&service=Router+interfaces&scroll=232.1666717529297

Current Status: CRITICAL

Status Information: CRITICAL: host '208.80.154.197', interfaces up: 229, down: 1, dormant: 0, excluded: 0, unused: 0:
xe-4/2/0: down -> Transport: cr2-eqord:xe-0/1/5 (Telia, IC-314533, 29ms) {#3658} [10Gbps wave];
https://wikitech.wikimedia.org/wiki/Network_monitoring#Router_interface_down

Last State Change: 2019-03-14 14:55:31

Event Timeline

Restricted Application added a subscriber: Aklapper. · View Herald Transcript

I sent an email to Telia with the circuit ID and time. They responded saying "Its up now ? There is no scheduled maintenance from our side. " and i said No, it's still down, our monitoring shows it down on both ends.

Telia claims the issue was resolved. our monitoring can't confirm that.

Telia Carrier Case Reference 	00959377
Service ID 	IC-314533
Service Type 	DWDM - 10 Gigabit - Ashburn - Chicago
Case Opened 	2019-03-14 15:38 UTC
Case Resolved 	2019-03-14 15:38 UTC
Summary 	We checked and there was a LOS from your side in Ashburn.
Please let us know if you need any further assistance from us.
ayounsi subscribed.

We're getting one way light, followed up with Telia.

Ashburn side:

Physical interface: xe-4/2/0
    Laser bias current                        :  43.070 mA
    Laser output power                        :  0.7540 mW / -1.23 dBm
    Receiver signal average optical power     :  0.3297 mW / -4.82 dBm

Chicago side:

Physical interface: xe-0/1/5
    Laser bias current                        :  45.520 mA
    Laser output power                        :  0.7260 mW / -1.39 dBm
    Laser receiver power                      :  0.0001 mW / -40.00 dBm

Telia did a loop test facing eqiad and our light levels didn't change. While Telia still don't receive light.
The culprit seems to be an active element somewhere on the cr2-eqiad (in DC6)<->Telia (in DC2) X-connect path.

Opened a ticket with Equinix to check the X-connect.

Link is back up. Cf. email thread for full details. But tl;dr; outdated cable label caused onsite tech to unplug our link.