TASK AUTO-GENERATED by Nagios/Icinga RAID event handler
A degraded RAID (megacli) [[ https://icinga.wikimedia.org/cgi-bin/icinga/extinfo.cgi?type=2&host=db1054&service=MegaRAID | was detected ]] on host `db1054`. An automatic snapshot of the current RAID status is attached below.
Please **sync with the service owner** to find the appropriate time window before actually replacing any failed hardware.
```
CRITICAL: 1 failed LD(s) (Degraded)
$ sudo /usr/local/lib/nagios/plugins/get_raid_status_megacli
=== RaidStatus (does not include components in optimal state)
name: Adapter #0
Virtual Drive: 0 (Target Id: 0)
RAID Level: Primary-1, Secondary-0, RAID Level Qualifier-0
State: =====> Degraded <=====
Number Of Drives per span: 2
Number of Spans: 6
Current Cache Policy: WriteBack, ReadAheadNone, Direct, Write Cache OK if Bad BBU
Span: 4 - Number of PDs: 2
PD: 0 Information
Enclosure Device ID: 32
Slot Number: 8
Drive's position: DiskGroup: 0, Span: 4, Arm: 0
Media Error Count: 25
Other Error Count: 4
Predictive Failure Count: 0
Last Predictive Failure Event Seq Number: 0
Raw Size: 558.911 GB [0x45dd2fb0 Sectors]
Firmware state: =====> Failed <=====
Media Type: Hard Disk Device
Drive Temperature: 34C (93.20 F)
=== RaidStatus completed
```